Subject to changes due to technical improvements ESS Energie Systeme & Service GmbH
34 CHP accessory range – 01/2010
5368 463
6.5.2 Load controller
Article number CHP module type ESS Viessmann
For all CHP module types except EM-18/36 710-00-0053 7411205
Function Load controller to prevent electrical power being fed into the public grid when a CHP module is being
operated in mains parallel mode.
Power modulation:
A value for the power still to be drawn from the public grid can be freely entered.
The CHP module generates power and heat simultaneously. During power modulation there may be
insufcient or excess heat.
With an adjustable start threshold (e.g. load 60 kW
el
), the CHP module is selected via a zero volt contact.
The module is subsequently regulated to the set minimum load (e.g. 10 kW
el
), using a default value (0 -
20 mA equates to 50 - 100 % electrical module output).
The digital display shows the current load (e.g. 10 kW
el
), the actual output demand (e.g. 60 kW
el
) and the
module default value (e.g. 50 kW
el
).
If the load drawn from the grid increases (actual output demand), the module is modulated up to the
maximum output. If the load drawn from the grid drops, the module output is reduced down to the
minimum output (50 %) and shut down at an adjustable stop threshold (e.g. load 30 kW
el
).
Please note that values below the minimum output value (50 %) cannot be regulated.
Furthermore, please note that a minimum load drawn from the grid or a minimum control grid feed-in
is always selected. If the module is regulated to exactly zero grid load, a "mains power failure" can no
longer be detected and at "power supply restoration", this would lead to asynchronous control.
Standard delivery Load controller in separate wall mounted casing
Control panel: 300 x 300 x 210 mm (H/W/D)
IP rating: IP41
Colour: RAL 7035
Max. ambient temperature: 45 °C
Max. relative humidity: 70 %
VDE: 0660/500
Cable entry: either top/bottom right
Door hinges: right
With the following integral parts:
PLC standard module with digital and analogue I/O module and internal control terminal
Fuse 24 VDC
Isolating amplier for separating the on-site load signal
Interface relay to enable module selection
(Power supply 24 VDC from module control eld)
Control panel complete with all necessary fuses and relays, wired to terminals ready for connection.
The wiring required between control unit and load signal is installed on site.
On-site requirements:
• Load signal - x kW to + y kW equates to 0 - 20 mA
or 4 - 20 mA
or 0 - 10 V
(The values x and y can be freely selected according to on-site conditions or requirements.)
Delivery As loose accessories for on-site installation
Electronics
6