Viessmann ESS CHP Especificações Página 19

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 40
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 18
Subject to changes due to technical improvements ESS Energie Systeme & Service GmbH
CHP accessory range – 01/2010 19
5368 463
5.3 Heating water connection set
Version See Viessmann catalogue
Note To complete the heating water connection set, the installation of a heating water pump is additionally
required. It should be sized on site to the required delivery head (and possibly delivery ow rate). (For a
recommendation for heating water pump sizing, see 0). If using a variable speed pump, an input signal of
0-10V is required if the return temperature raising facility is not used.
The shut-off valves for Vitobloc 200 EM-238/363, EM-363/498, EM-401/589 and BM-366/437 should be
ordered separately:
EM-238/363 2 shut-off valves DN 65
EM-363/498, EM-401/589, BM-366/437 2 shut-off valves DN 80
Heating water connection set
Viessmann article no. corresponding to CHP type
EM-18/36
EM-50/81
EM-70/115
BM-36/66
BM-55/88
EM-149/207
BM-98/150
BM-123/177
EM-199/263
EM-199/293
BM-190/238
EM238/363
EM-363/498
EM-401/549
BM-366/437
Part no. Z007326 Z007327 Z007328 Z007328 Z007329 Z008582
Standard delivery
Expansion vessel 9572214 9572214 9572212 9572212 9572215 9572904
Cap valve 9572213 9572213 9572213 9572213 9572213 9572213
Fitting block with pressure gauge 7188380 7188380 7188380 7188380 7188380 7188380
Retainer 9572216 9572216
Safety valve 9572222 9572222 9572226 9572991 9572991 9572992
Thermometer 2 x 9034009 2 x 9034009 2 x 9034009 2 x 9034009 2 x 9034009 2 x 9034009
Shut-off valves 2 x 9572262 2 x 9572263 2 x 9572264 2 x 9572264
Drain 7143894 7143894 7143894 7143894 7143894 7143894
Module details
CHP module type
EM-18/36
EM-50/81
BM-36/66
EM-70/115
BM-55/88
EM-140/207
BM-98/150
BM-123/177
EM-199/263
EM-199/293
BM-190/238
EM-238/363
EM-363/498
EM-401/549
BM-366/437
Temperature delta in K 15 20 20 20 20 20 20
Flow rate in m³/h 2.1 3.5 4.9 8.9 12.6 23.5 15.6
Connection DN 25 DN 40 DN 40 DN 50 DN 65 DN 65 DN 80
Pressure drop in m* 4 6 6 7 9 9 9
Pump recommendation
Manufacturer Grundfos Grundfos Grundfos Grundfos Grundfos Grundfos Grundfos
Type Magna 25-60 Magna 32-100 Magna 32-100 Magna 40-120 Magna 50-120 Magna 50-120 F Magna 65-120 F
Int. diameter DN 25 DN 32 DN 32 DN 40 (32) DN 50 DN 50 DN 65
Voltage in V 230 230 230 230 230 230 230
Delivery head range in m 0.5..6 0.5..11.5 0.5..11.5 0.5..12.5 0.5..13 0.5..13 0.5..13
Flow rate range in m³/h
0..8.5 0..11.5 0..11.5 0..22.5 0..32 0..32 0..38
Delivery head at CHP
nominal ow rate in m at
speed stage
only variable
speed
7.5
1
7.5
1
7.5
2
9.5
3
10.5
variable speed
12.0
variable speed
Heating
5
Tab. 1 Article numbers of components in the heating water connection set in the Viessmann catalogue
* Including plate heat exchanger, return temperature raising facility, heat meter, dirt trap, connectors, shut-off valves etc. (guide values)
Tab. 2 Recommendation for heating water pump sizing
Vista de página 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 39 40

Comentários a estes Manuais

Sem comentários