Subject to changes due to technical improvements ESS Energie Systeme & Service GmbH
18 CHP accessory range – 01/2010
5368 463
5 Heating
5.1 Higher heating water return temperatures
Article number CHP module type ESS Viessmann
EM-50/81, EM-70/115 710-00-0035 7417749
EM-140/207 710-00-0036 7417750
EM-238/363 710-00-0037 7417751
Version Equipped with larger heat exchanger and if required matched cooling water pump
Function Higher heating water return temperatures 90 / 75 °C, e.g. for operation with an absorption cooling
system
• Please note: Heating output reduced by 5 % with the same energy usage
• Please note: After inspection, there may be additional maintenance costs due to the thermal load
of the engine oil
Delivery Fitted in the CHP module
5.2 Heating water temperature control
Version See Viessmann catalogue
Function See Viessmann catalogue
The Vitobloc 200 contains a controller with a continuous output signal 0..10 V as standard. Via an on-
site mixing valve with servomotor, it regulates either the heating water return temperature or an on-site
variable speed heating water pump for a constant ow temperature.
Note Biogas modules should always be tted with a heating water return temperature raising facility!
Note for mixer
Valve ow rate at 100 % lift
Heating water ow rate
Pressure drop
Tab. 4 Sizing the components in the heating water return temperature raising assembly
Heating
5
CHP module type
EM-50/81
EM-70/115
BM-36/66
BM-55/88
EM-149/207
BM-98/150
BM-123/177
EM-199/263
EM-199/293
BM-190/238
EM-238/363
EM-363/498
EM-401/549
BM-366/437
Three-way valve body
Internal diameter DN 40
threaded connection
with tting PN 16
k
VS
value 25 m
3
/h
Internal diameter DN 50
Flange PN 16
k
VS
value 40 m
3
/h
Internal diameter DN 65
Flange PN 16
k
VS
value 63 m
3
/h
Internal diameter DN 80
Flange PN 16
k
VS
value 180 m
3
/h
Comentários a estes Manuais