23 |
SCU224
a b
Tanks are cooled during the night.
Does collector circuit
pump run during the
night?
no yes
Check the controller
functions
Collector temperature is
at night higher than ambi-
ent temperature.
no yes
Check the supply and re-
turn line flow check valves
to ensure functionality.
Is the tank insulation
sufficient?
yes no
Intensify the insulation.
Is the tank insulation clo-
se enough to the store?
yes no
Replace or intensify the
insulation.
Are the tank connections
insulated?
yes no
Insulate connections.
Warm water outflow
upwards?
no yes
Change connection and
let the water flow side-
wards or through a ther-
mosiphon trap; less tank
losses now?
Does warm water re-
circulation pump run for
a very long time?
no yes
Use the re-circulation
pump with timer and
switch-off thermostat (en-
ergy efficient circulation)
The solar circuit pump does not work although the colle-
ctor is obviously warmer than the tank.
Does the control LED
flash?
yes no
Does the pump start up
in manual operation?
yes
There is no current; check
fuses / replace them and
check power supply.
The adjusted tempe rature
difference for starting the
pump is too high; choose
a matching setting
no
Is the power supply to
the pump coming from
the controller?
yes
Is the pump stuck?
Put the pump into operati-
on by means of a screwdri-
ver; is it passable now ?
Is the pump out of order?
- replace if necessary
Are the fuses o.k.?
Controller seems to be
defective - replace it.
no
yes
no
no yes
Replace the fuses.
Switch-off the re-circulati-
on pump and the isolation
valve for 1 night; less tank
losses?
yes no
Check the pumps of the
after-heating circuit ac-
cording to nightly run and
defective check valve; pro-
blem solved?
no
no yes
o.k.
Control the check valve
in warm water circulati-
on- o.k.
yes no
Please also check further
pumps which are con-
nected to the solar tank.
The gravitation circu-
lation in the circulation
line is too strong; insert a
stronger check valve or an
electrical 2-way valve be-
hind the circulation pump;
the 2-way valve is open in
pump operation, other-
wise it is closed, conect
pump and 2-way valve in
parallel; activate the cir-
culation again!
Cleaning or replacement.
a
a b
b