© 08284 SCU224.monus.indd
17 |
SCU224
4.1.8∆T-regulation
DT O:
Switch-on temperature
difference
Adjustment range
2,0 ... 40,0 °Ra
Factory setting 12.0
DT F / DT1F / DT2F / DT3F:
Switch-off temperature
difference
Adjustment range 1,0 ... 38,0°Ra
Factory setting 8,0°Ra
4.1.9Tankmaximumtemperature
If the adjusted maximum tank temperature is exceeded,
further heating of the tank is stopped so that damaging
overheating can be avoided. If the maximum tank temperature
is exceeded, the display will show the symbol
.
Please note: The controller is equipped with a security-
switch-off of the tank, which avoids further heating of the
tank if 203 °F is reached at the tank.
S MX / S1MX / S2MX:
Maximum tank temp.
Adjustment range 40 ... 203 °F
Factory setting 140 °F
Primarily the controller looks at the temperature difference
between the collector temperature sensor and the tank
temperature sensor. If the switch-on temperature difference
(DT O / DT1O / DT2O) is reached, the pump is activated.
If the adjusted switch-off temperature is underrun (DTF /
DT1F / DT2F), the controller switches-off.
Maximum temperature limitation
The controller is equipped with an independent tempe-
rature differential regulation for which minimum and
maximum temperature limations as well as corresponding
switch-on and -off temperatures can be separately adjusted.
Only possible for Arr = 2 and 8 (e.g. for solid fuel boilers or
heat exchange regulation).
If the adjusted value MX3O is exceeded, relay 2 will
be deactivated. When falling below MX3F, the re-
lay will be switched on again.
Reference sensor:
S3 by Arr 8 (TSTU)
S4 by Arr 2 (TST2)
Is the adjusted value MN3O underrun, relay 2 will be
deactivated. By falling below MN3F, the relay will be
switched on again.
Reference sensor:
S4 by Arr 8 (TFSB)
S3 by Arr 2 (TSTU)
Both switch on- and switch off temperature differences
DT3F and DT3O apply parallely for the maximal- and
minimal temperature limit.
MX3O / MX3F:
Maximum temperature limi-
tation
Adjustment range 30 ... 205°F
Factory setting
MX3O 140°F
MX3F 136°F
Minimum temperature limitation
MN3O / MN3F:
Minimum temperature limi-
tation
Adjustment range 30 ... 195°F
Factory setting:
Arr = 2
MN3O 40°F
MN3F 50F
Arr = 8
MN3O 140°F
MN3F 150°F
4.1.10 ∆T-controller (solid fuel boiler and heat exchange)
Please note: Switch-on temperature difference DT O must
be at least 2 °Ra higher than the switch-off tempe rature-
difference DF.