5.1Various:
Pump starts for a short moment, switches-on/off
repeatedly
Is the temperature diffe-
rence at the controller
too small?
no yes
Wrong placing of the
collector sensor?
yes
Change∆Ton and ∆Toff
accordingly.
Mount the collector sen-
sor at solar feed flow
(warmest collector out-
put); use the sensor well of
the respective collector.
Pump starts up very late and stops working soon.
The temperature difference between tank and collector
increases enormously during operation; the collector cir-
cuit cannot dissipate the heat.
Collector circuit pump
defect ?
no yes
Heat exchanger calcified?
yes
Repair / Replace
Decalification
no
Heat exchanger plugged?
yesno
Cleaning
Heat exchanger too
small?
yes
New calculation of the
dimension.
no
Activate option tube coll-
ector special function
Change∆Ton and ∆Toff
accordingly.
Switch-on-temperature
difference ∆Ton too
large?
no yes
Collector sensor un favour-
able placed (e.g. contact
sensor instead of sensor
well.
o.k.no
Pump is overheated, but no heat is being transferred from
collector to the tank, feed flow and return flow are equally
warm, possibly also bubble in the tubes
Exhaust the system; incre-
ase system pressure to
the minimum pressures
listed in the Vitosol Start-
up and service manual.
Switch the pump on and
off for a short time
Air in the system?
no yes
Is the collector circuit
blocked at the dirt trap?
yes
Clean the dirt trap
If necessary activate tube
collector function.
yes
o.k.