Viessmann SCU224 Manual de Serviço Página 31

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 30
© Viessmann 5443203
31 |
SCU224
Legend:
Symbol Specification
x Channel is available
x* Channel is available if the corresponding option is activated.
s Channel is specifically available in this system layout
Adjustment Channels
Channel Description Factory setting Page
Arr x System 10 39
DT O x Switch-on temperature difference 12.0 °Ra [6.0 K] 39
DT F x Switch-off temperature difference 8.0 °Ra [4.0 K] 39
DT S x Nominal temperature difference 20.0 °Ra [10.0 K] 39
RIS x Rise control R1 4 °Ra [2 K] 39
nMN x Minimum pump speed 30 % 39
S MX x Maximum tank temperature 140 °F [60 °C] 40
EM x Emergency temperature collector 270 °F [130 °C] 40
CMX s Maximum collector temperature
230 °F [110 °C] 41
OCN x Option minimum limitation OFF 42
CMN x* Minimum collector temperature 50 °F [10 °C] 42
OCF x Option antifreeze OFF 42
CFR x* Antifreeze temperature 40.0 °F [4.0 °C] 42
O TC x Option tube collector OFF 44
TCST x* OTC starting time 07:00 44
TCEN x* OTC ending time 19:00 44
TCRU x* OTC runtime 30 s 44
TCIN x* OTC standstill interval 30 min 44
OHQM x Option energy metering OFF 44
FMAX x* Maximum flow 6.0 l 44
MEDT x* Antifreeze type 1 44
MED% x* Antifreeze concentration (only if MEDT = propylene or ethylene) 45 % 44
MAN1 x Manual operation R1 Auto 46
MAN2 x Manual operation R2 Auto 46
LANG x Language En 46
UNIT x Temperature unit °C 46
RESE x Reset - back to factory defaults 46
W0050100 Version number
Vista de página 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 51 52

Comentários a estes Manuais

Sem comentários