System layout 6
The controller calculates the temperature differences
between collector sensor S1 and tank sensors S2 and S3. If
the differences are larger than or identical to the adjusted
switch-on temperature differences (DT1O / DT2O), the
solar pumps will be operated by relay 1 and / or relay 2,
and the respective tank will be loaded until the switch-off
temperature differences (DT1F / DT2F) or the maximum
Arr 6
Tank 1
Tank 2
S4
Display Channels
Channel Description Terminal Page
COL x Temperature collector S1 37
TST1 x Temperature tank 1 bottom S2 37
TST2 x Temperature tank 2 bottom S3 37
S4 x Temperature sensor 4 S4 37
n1 % x Pump speed R1 R1 38
n2 % x Pump speed R2 R2 38
h P1 x Operating hours R1 R1 38
h P2 x Operating hours R2 R2 38
TIME x Time - 34
tank temperatures (S1MX / S2MX) are reached. The priority
logic causes priority loading of the selected tank (PRIO), if
possible. Loading both tanks simultaneously is possible as
well (PRIO = 0).
Sensor S4 can optionally be connected for measurement
purposes.