System layout 5
The controller calculates the temperature differences
between collector sensor S1 and tank sensors S2 and S3. If
the differences are larger than or identical to the adjusted
switch-on temperature differences (DT1O / DT2O), the so-
lar pump will be operated by relay 1, and the respective tank
will be loaded until the switch-off temperature differences
(DT1F / DT2F) or the maximum tank temperatures (S1MX /
R2
S4 / TR
S1
R1
S2 S3
Arr 5
Tank 1
Tank 2
Display Channels
Channel Description Terminal Page
COL x Temperature collector S1 37
TST1 x Temperature tank 1 bottom S2 37
TST2 x Temperature tank 2 bottom S3 37
S4 x Temperature sensor 4 S4 37
TR x* Temperature return sensor S4 37
n % x Pump speed relay R1 38
hP1 x Operating hours R1 R1 38
hP2 x Operating hours R2 R2 38
kWh
x*
Heat quantity kWh - 38
MWh
x*
Heat quantity MWh - 38
TIME
x
Time - 34
S2MX) are reached. The priority logic causes priority loading
of tank 1, if possible. For loading tank 2 the 3-way-valve will
be operated by relay 2.
Sensor S4 can optionally be connected for measurement
purposes.
If energy metering (OHQM) is activated, sensor S4 has to
be connected as return sensor.