Venting the boiler
1. Clos e the shut-off valves on th e pri-
mary side.
2. Connect the drain hose on valve
A with a drain outlet.
3. Open valve A andfillvalveinthe
heating return and vent at mains
pressure, until no sound of escap-
ingaircanbeheard.
4. Clos e valve A and fill valve in the
heating return and open the pri-
mary shut-off valves.
Venting the heating system
1. Clos e the gas shut-off v alve and
switch ON the control unit.
2. Activate the venting program via
code "2F:1".
Note
To call up codin g level 1 an d for
setting the coding address, see
page 39.
For the function and sequence of
the venting progr am, see page 100.
Whilst the venting program runs,
the display shows "EL"
(Vitotronic 100) or "Venting"
(Vitotronic 200).
3. Check the system pressure.
Further details regarding the individual steps (cont.)
8
Initial start-up, inspection, maintenance
5692 619 GB