Filling the heating system
!
Please note
Unsuitable fil l water increases the level of depo sits and corrosio n and
may lead to boiler damage.
&
Thoroughly flush the entire heating system prior to filling with water.
&
Only use fill water of p otable quality.
&
Fill water with a water ha rdness in excess of 3.58 mmo l/l must be sof-
tened, e.g. with t he small softening sys tem for heating wate r (see the
Vitoset pricelist).
&
An anti-freeze additive suitable for heating systems can be mixed with
the fill water.
1. Check t he inlet pres sure of the di a-
phragm expansion vessel.
2. Clos e the gas shut-off v alve.
3. Fill the h eating system at the fill
valve in the heati ng return (on the
connection set or on si te). Minimum
system pressure > 0.8 bar).
Note
If the control uni t has not been
switched ON prior to filling the sys-
tem, then the servomotor of the
changeover valve will still be in its
centre position , and the system will
be completely filled.
4. If the control unit had already been
switched ON before filling began:
Start the control u nit and activate
thefillprogramviacoding"2F:2".
Note
To call up codin g level 1 an d for
setting the coding address, see
page 39.
For function and details of the fill
program, see page 100.
Whilst the fill program runs, the dis-
play shows "bF" (Vitotronic 100) or
"Filling" (Vitotronic 200).
5. Close the boiler fill & drain valve.
6. Set code "2F:0".
Further details regarding the individual steps
7
Initial start-up, inspection, maintenance
5692 619 GB