1. Connect a flue gas analyser at the
flue gas aperture A on the boiler
adaptor.
2. Open the gas shut-off valve, com-
mission the boiler and create a heat
demand.
3. Select the lower rated output.
Constant temperature control unit:
&
Press both keys 9 and d simul-
taneously until th e display shows
1.
Weather-compensated control unit:
&
Press both keys 9 and d simul-
taneously until th e display shows
Relay test.
&
With a/b in the display, select
Basic load.
4. Check the CO
2 content. Should the
actual value deviate by more than
1 % from the above range, imple-
ment steps from p age 15 (possib ly
replace the burn er).
5. Enter actual values into the service
report.
6. Set the upper rated output.
Constant temperature control unit:
&
With a/b in the display, select
2.
Weather-compensated control unit:
&
With a/b in the display, select
Full load.
Further details regarding the individual steps (cont.)
16
Initial start-up, inspection, maintenance
5692 548 GB