Point Point Description Unit
AI1 Boiler 1 actual temperature °C/°F Y Y Y Y Y Y
AI2 Boiler 1 actual return temperature sensor 1 (17A for GC1/GC1B) °C/°F Y N N Y Y N
AI3 Boiler 1 modulation °C/°F Y N N Y Y Y
AI4 Boiler 1 flue gas actual temperature °C/°F Y Y Y Y Y N
AI5 Boiler 1 fault code (Appendix A) N/A Y Y Y Y Y N
AI6 Boiler 1 relay state (Appendix B) N/A Y Y Y Y Y N
AI7 Boiler 2 actual temperature °C/°F N N N N Y Y
AI8 Boiler 2 actual return temperature sensor 1 (17A for GC1/GC1B) °C/°F N N N N Y N
AI9 Boiler 2 modulation °C/°F N N N N Y Y
AI10 Boiler 2 flue gas actual temperature °C/°F N N N N Y N
AI11 Boiler 2 fault code (Appendix A) N/A N N N N Y N
AI12 Boiler 2 relay state (Appendix B) N/A N N N N Y N
AI13 Boiler 3 actual temperature °C/°F N N N N Y Y
AI14 Boiler 3 actual return temperature sensor 1 (17A for GC1/GC1B) °C/°F N N N N Y N
AI15 Boiler 3 modulation °C/°F N N N N Y Y
AI16 Boiler 3 flue gas actual temperature °C/°F N N N N Y N
AI17 Boiler 3 fault code (Appendix A) N/A N N N N Y N
AI18 Boiler 3 relay state (Appendix B) N/A N N N N Y N
AI19 Boiler 4 actual temperature °C/°F N N N N Y Y
AI20 Boiler 4 actual return temperature sensor 1 (17A for GC1/GC1B) °C/°F N N N N Y N
AI21 Boiler 4 modulation °C/°F N N N N Y Y
AI22 Boiler 4 flue gas actual temperature °C/°F N N N N Y N
AI23 Boiler 4 fault code (Appendix A) N/A N N N N Y N
AI24 Boiler 4 relay state (Appendix B) N/A N N N N Y N
AI25 Zone/Cascade/Boiler Outdoor temperature °C/°F N Y Y Y Y Y
AI26 Zone/Cascade/Boiler Relay State (Appendix B) N/A N Y Y Y Y Y
AI27 Zone/Cascade/Boiler Fault Code (Appendix A) N/A N Y Y Y Y Y
AI28 Zone/Cascade/Boiler DHW Set-Point °C/°F Y Y Y Y Y Y
AI29 Zone/Cascade/Boiler DHW Actual Temperature °C/°F Y Y Y Y Y Y
AI30 Zone/Cascade/Boiler Zone A1 Supply Set-Point °C/°F Y Y Y Y Y Y
AI31 Zone/Cascade/Boiler Zone A1 Supply Actual Temperature °C/°F N Y Y Y Y Y
AI32 Zone/Cascade/Boiler Zone A1 Actual Return Temperature °C/°F N N N Y Y Y
AI33 Zone/Cascade/Boiler Zone A1 Curve Shift °K N Y Y Y Y Y
AI34 Zone/Cascade/Boiler Zone A1 Curve Slope N/A N Y Y Y Y Y
Points Available Y/N
Analog Inputs
Values which can be read from the Versatronik 505 NR2/BACIP Gateway
Analog Input Overview
Vitotronic 100, GC1
Vitodens 200, B2HA
Vitotronic 200, HO1
Vitotronic 300, GW2
Vitotronic 333/300-K MW1
Vitotronic 300-K, MW2**
Note:
Temperature values only possible with specific
installed sensors based on particular installation
**Vitodens boilers which communicate via KMK to the 300-K MW2B may
not provide some points of information that LON communication does.
Boiler/burner faults do not appear directly from the boiler. It is necessary
to pick up the burner/boiler fault from the Cascade Fault Status.